Hope65 digital inputs are used for external RUN, forward, reverse, jog, reset, free stop, external fault, multi-speed selection, terminal UP/DOWN, and other ON/OFF command functions. Smaller Hope65S2 0.75–1.5 kW models provide DI1 to DI4, with DI4 usable as a high-speed pulse input. Larger Hope65GS2 2.2–5.5 kW and Hope65GT4 0.75–22 kW models provide DI1 to DI5, with DI5 usable as a high-speed pulse input.
If the motor runs from keypad but does not run from external terminals, check four items first: F0-21 command source, F6 DI function assignment, J12 source/sink jumper position, and DI active-high/active-low setting.
For reliable operation, use shielded DI cables where possible, keep digital input wiring short, avoid running DI wires with motor U/V/W cables, and confirm whether the external device is contact, relay, NPN, PNP, sinking output, or sourcing output before wiring.
Only trained and qualified electrical personnel should wire, modify, test, or troubleshoot Hope65 control terminals and panel control circuits.
Before touching wiring or terminals, switch off all input power, wait at least 10 minutes, and confirm that the DC bus voltage has discharged to a safe level. Do not change DI wiring while the drive or panel is energized.
This article explains how to wire and configure Hope65 Series Smart AC Drive / VFD digital input terminals. It is designed for technicians, panel builders, machine integrators, PLC engineers, and maintenance teams who need to start and stop the drive using external switches, push buttons, sensors, PLC outputs, or interlock circuits.
Digital input wiring is one of the most common reasons for field commissioning issues. A drive can be perfectly healthy and still refuse to start if the command source is wrong, the DI terminal function is not assigned, the source/sink jumper does not match the PLC output, or the active-high/active-low logic is inverted. This guide separates those issues step by step.
01 Wire CorrectlyConfirm contact, NPN, PNP, source, sink, internal 24V, or external 24V method before connecting DI. | 02 Assign FunctionSet the required F6 function for each DI: forward, reverse, jog, reset, fault, free stop, multi-speed, etc. | 03 Select LogicSet active-high or active-low and select two-wire or three-wire command mode to match the machine panel. |
| Product Series | Slanvert Hope65 Series Smart AC Drive / VFD |
| Small Models | Hope65S2 / Hope65GS2 0.75 kW to 1.5 kW class models with DI1–DI4. DI4 can be used as high-speed pulse input. |
| Larger Models | Hope65GS2 2.2 kW to 5.5 kW and Hope65GT4 0.75 kW to 22 kW class models with DI1–DI5. DI5 can be used as high-speed pulse input. |
| Control Devices Covered | Selector switches, push buttons, relay contacts, PLC outputs, NPN sensors, PNP sensors, dry contacts, interlocks, external fault contacts, and jog/reset buttons. |
| User Level | Qualified electrical technician, panel builder, machine integrator, maintenance engineer, or automation engineer. |
A Hope65 digital input command works only when the physical wiring, jumper setting, input function, active state, and command source all match each other.
01 Field Device
| → | 02 DI Terminal
| → | 03 F6 Logic
|
04 Command Source
| → | 05 Drive Action
| Main Rule: If any one item in the command chain is wrong, the VFD may ignore the external command even though the wiring looks correct. | |
| Hope65 Model Group | Digital Inputs | High-Speed Pulse Input | Notes |
|---|---|---|---|
| Hope65S2 / Hope65GS2 0.75–1.5 kW | DI1, DI2, DI3, DI4 | DI4 | Use F6-00 to F6-03 for DI function assignment. |
| Hope65GS2 2.2–5.5 kW and Hope65GT4 0.75–22 kW | DI1, DI2, DI3, DI4, DI5 | DI5 | Use F6-00 to F6-04 for DI function assignment. |
Each DI terminal must be assigned a function in the F6 group. The same physical DI terminal can be used for different functions depending on the application.
| Function Value | Function Name | Typical Use | Important Note |
|---|---|---|---|
| 0 | No function | Unused DI terminal. | Set unused terminals to no function to avoid accidental operation. |
| 1 | Forward run / run command | External start or forward command. | Must be matched with terminal command mode. |
| 2 | Reverse run / direction command | Reverse operation or direction selection. | Use only where reverse rotation is mechanically safe. |
| 3 | Three-wire operation control | Three-wire push-button station. | Requires terminal command mode set for three-wire logic. |
| 4 / 5 | Forward jog / reverse jog | Manual inching during setup or maintenance. | Confirm jog frequency and jog ramp before use. |
| 6 / 7 | Terminal UP / DOWN | Increase or decrease frequency from external buttons. | Equivalent to holding UP/DOWN command. |
| 8 | Free stop | Coast-to-stop command. | Machine may coast; not a replacement for safety-rated stop. |
| 9 | Fault reset | External reset button or PLC reset output. | Do not repeatedly reset before correcting fault cause. |
| 10 | Running pause | Pause running while retaining operation state. | Check sequence behavior before using in production. |
| 11 | External fault input | Fault input from another device or interlock. | Wrong active logic can create continuous E15/A15 fault. |
| 12–15 | Multi-segment command terminals | Preset speed or multi-step command selection. | DI combinations can select multiple speed states. |
Source/sink wiring defines the direction of current flow through the digital input circuit. In the field, this usually appears as NPN or PNP sensor/PLC output wiring. The Hope65 uses jumper J12 PW to select the suitable source-type or sink-type digital input method.
Contact Control Uses dry contact, selector switch, push button, or relay contact. This is the simplest and recommended method for many panels. | NPN / Sink Output Device Common in PLC/sensor wiring where the device pulls the input path toward 0V/common when active. | PNP / Source Output Device Common in PLC/sensor wiring where the device supplies positive voltage to the input when active. |
| Important: NPN/PNP terminology can vary between field devices and regions. Always verify the PLC/sensor manual and check whether the output is sinking or sourcing before connecting to the VFD. | ||
J12 is the key jumper for source/sink digital input wiring. The wrong jumper setting is a common cause of terminal start failure.
| Jumper | Position | Function | Use Case |
|---|---|---|---|
| J12 PW | 1–2 | Source-type wiring method. | Factory-default style wiring method. Use when the field wiring method matches source-type input arrangement. |
| J12 PW | 2–3 | Sink-type wiring method. | Use when the field wiring method requires sink-type input arrangement. |
| J12 removed from PW/+24V link | External power supply wiring | Used when DI circuit is driven using external 24V supply. | Required in external power supply NPN/PNP wiring methods as per manual wiring approach. |
Hope65 DI terminals can be controlled using the VFD’s internal 24V supply or an external 24V source depending on the panel design. The wiring method must not mix commons incorrectly.
| Wiring Method | How It Works | When to Use | Risk If Wrong |
|---|---|---|---|
| Internal 24V + contact control | Uses VFD 24V/COM and external dry contacts to activate DI. | Simple push button, selector switch, relay contact, local panel control. | Wrong common or short circuit can prevent DI activation or damage control supply. |
| Internal 24V + NPN/PNP device | Uses Hope65 auxiliary 24V and a compatible sensor/PLC output method. | Small local field devices with compatible current requirement. | Wrong source/sink selection causes DI not to respond. |
| External 24V + NPN/PNP controller | Uses external panel 24V supply and common reference to control DI. | PLC panel, multi-device control, isolated control supply design. | If jumper/common is wrong, DI can stay always ON, always OFF, or behave erratically. |
The DI terminal active mode determines whether a short-circuited/energized DI state is treated as valid or invalid. This is separate from the physical wiring method.
| DI Active Mode | Meaning | Typical Symptom If Wrong |
|---|---|---|
| Active high | The DI terminal is valid when it is activated/short-circuited according to the selected wiring method. | If wiring expects active low, the command may not work until the contact state is reversed. |
| Active low | The DI terminal is valid when the corresponding signal is disconnected/inactive according to active-low setting. | Start/stop, external fault, or reset may appear inverted or continuously active. |
Two-wire control is common when the drive is controlled by maintained selector switches or PLC maintained outputs. The command remains active as long as the DI state remains active.
DI1 Forward running command. | DI2 Reverse running command. | Stop State If both are OFF or both are ON at the same time, the VFD stops in this mode. |
| Control Mode | DI1 | DI2 | Result |
|---|---|---|---|
| Two-wire mode 1 | ON | OFF | Forward run |
| Two-wire mode 1 | OFF | ON | Reverse run |
| Two-wire mode 1 | OFF | OFF | Stop |
| Two-wire mode 1 | ON | ON | Stop / invalid direction condition |
Three-wire control is used when the machine uses push buttons instead of maintained switches. In three-wire operation, one DI normally works as the enable/stop path, while other DI terminals provide momentary start/direction commands.
| Three-Wire Mode | DI Arrangement | How It Works | Common Mistake |
|---|---|---|---|
| Three-wire mode 1 | DI3 = enable / three-wire control, DI1 = forward, DI2 = reverse | Enable must remain active. Forward/reverse commands are accepted when the respective push button is pressed. | Enable/stop circuit is open, so start buttons do nothing. |
| Three-wire mode 2 | DI3 = enable, DI1 = run command, DI2 = direction state | DI1 starts operation while DI2 determines direction according to its state. | Panel push-button wiring does not match selected three-wire logic. |
Digital input wiring requires matching parameter setup. The exact parameter number differs slightly by model group, so confirm with the drive model and the manual.
| Parameter / Group | Purpose | When to Check |
|---|---|---|
| F0-21 | Selects command source: keypad, terminal, or communication. | Set to terminal command when DI terminals must start/stop the VFD. |
| F0-02 | Selects frequency source. | Check when DI start works but motor speed remains 0 Hz. |
| F6-00 to F6-03 | DI1 to DI4 function assignment for small 0.75–1.5 kW models. | Check when assigning forward, reverse, jog, reset, external fault, or multi-speed functions. |
| F6-00 to F6-04 | DI1 to DI5 function assignment for larger models. | Check when assigning DI5 or pulse input functions on larger models. |
| DI active mode | Defines whether each DI is active-high or active-low. | Check when input behavior appears inverted or continuously active. |
| Terminal command mode | Selects two-wire mode 1, two-wire mode 2, three-wire mode 1, or three-wire mode 2. | Check when external start/stop wiring does not behave as expected. |
| DI filter time | Filters interference on DI terminals. | Increase carefully when DI terminals are disturbed by noise; longer filter slows response. |
| DI delay time | Adds response delay after DI signal is detected. | Use when sequence timing requires a deliberate delay. |
Hope65 allows AI1 to be used as a digital input through F6 parameter setup. This can be useful when additional DI logic is required, but it must be configured carefully.
| AI1 as DI Item | Behavior | Use Carefully Because |
|---|---|---|
| AI1 terminal function selection | AI1 can remain analog input or be assigned a DI function. | If AI1 is used as DI, it is no longer available as the normal analog speed input. |
| AI1 voltage threshold | AI1 is treated as high level above approximately 7V and low level below approximately 3V, with hysteresis between the two. | A floating or noisy voltage may cause unstable DI status. |
| AI1 as DI valid state | Can be set active-high or active-low. | Wrong valid-state setting can invert the command. |
Digital input wiring is more noise-tolerant than analog wiring, but it can still be affected by motor cable noise, poor grounding, long cable runs, inductive loads, and incorrect control common wiring.
| Wiring Practice | Recommendation | Issue Prevented |
|---|---|---|
| Cable type | Use shielded cable where possible. | False DI triggering and noise-related command behavior. |
| Cable length | Keep digital input wiring short, ideally not more than 20 m. | Signal pickup, delay, and unstable status. |
| Cable route | Do not route DI wiring with input power cable or U/V/W motor cable. | Random start/stop, false reset, external fault, or multi-speed switching. |
| Power crosstalk filtering | Use proper filtering when active drive mode is affected by power supply crosstalk. | False trigger from noisy 24V control supply. |
| DI filter time | Increase carefully only when site interference is confirmed. | Noise triggering while preserving response time. |
| Problem | Likely Cause | Corrective Action |
|---|---|---|
| Motor runs from keypad but not from DI start | F0-21 not set to terminal command, DI function not assigned, or terminal mode mismatch. | Set command source to terminal, assign DI run function, and select correct two-wire/three-wire mode. |
| DI status does not change | Wrong common, J12 mismatch, NPN/PNP mismatch, no 24V supply, or broken contact. | Verify voltage/common, check J12, confirm field device output type, and test with dry contact if safe. |
| Drive starts when switch is OFF | Active-high/active-low logic inverted or contact type wrong. | Correct DI active mode or change NO/NC wiring logic according to the machine design. |
| External fault remains active | External fault DI set active-low/active-high incorrectly, or interlock contact is open. | Check DI function value, active mode, interlock contact, and PLC output status. |
| DI command flickers or changes randomly | Noise pickup, long cable, poor shielding, common reference problem, or cable routed with motor wires. | Separate cable route, use shielded cable, check 24V common, and increase DI filter time if required. |
| Both forward and reverse commands stop the drive | Two-wire mode 1 sees both DI1 and DI2 active at the same time. | Modify PLC logic or selector switch wiring so only one direction command is active at a time. |
Use this checklist before releasing the machine for production.
To reduce troubleshooting time, share the following information:
Smidnya technical support can help review your DI wiring, J12 source/sink jumper position, PLC output type, F6 terminal settings, two-wire/three-wire command mode, and active-high/active-low logic before commissioning.