Hope65 VFD Control Terminal Wiring Guide | DI AI AO DO Relay RS485

Hope65 Series Smart AC Drive / VFD Control Terminal Wiring Guide

Slanvert Hope65 Series | Smidnya Control Wiring Guide
```

Hope65 Series Smart AC Drive / VFD Control Terminal Wiring Guide

Complete guide for Hope65 control wiring: digital inputs, analog input, analog output, digital output, relay output, RS485, 24V/COM, 10V/GND, source/sink wiring, jumpers, and terminal command setup.

DI1–DI5
Digital inputs
AI / AO
0–10V / 4–20mA
RS485
Modbus-ready port
Control Terminal Overview
Hope65 Control Side
COMMAND + SPEED + FEEDBACK
Separate signal wiring from motor and power cables




DI / AI / AO / DO / Relay / RS485
Configure terminals before external control
Start / StopSpeed Ref.
Fault OutputPLC / HMI
Use keypad test before final external control.
```

Quick Answer

```

Hope65 control terminals are used for external start/stop, forward/reverse, jog, reset, analog speed reference, relay fault output, digital output, analog output, and RS485 communication. Typical terminals include DI1–DI5, AI1, AO1, DO, 10V/GND, 24V/COM, RA/RB/RC, and RS485A/RS485B.

For external terminal control, first prove that the motor runs from the keypad. Then set the command source to terminal control, assign DI functions in the F6 group, select the correct two-wire or three-wire mode, confirm source/sink wiring, and verify whether the input logic is active-high or active-low.

For analog control, use shielded cable, keep the cable length short, confirm the AI jumper setting for 0–10V or 0/4–20mA, and route analog/RS485 wiring separately from power and motor cables.

```

Safety Warning Before Control Wiring

```

Only trained and qualified electrical personnel should wire or modify Hope65 control terminals, power terminals, motor terminals, or panel circuits.

Before touching terminals or wiring, switch off all input power, wait at least 10 minutes, and confirm that the DC bus voltage has discharged to a safe level. Do not change control wiring while the drive or panel is energized.

```

1. What This Article Helps You Do

This article explains how to wire and configure the Hope65 Series Smart AC Drive / VFD control terminals. It covers digital inputs for start/stop and reset, analog input for speed reference, analog output for feedback, digital output, relay output, RS485 communication wiring, 10V and 24V auxiliary supplies, source/sink logic, NPN/PNP field devices, jumper settings, and practical troubleshooting.

Use this guide when the motor runs from the keypad but does not run from external switches, PLC, HMI, potentiometer, analog signal, relay interlock, or Modbus control. This article focuses on control wiring and parameter logic, not main power wiring. Power wiring should already be verified before control-side troubleshooting.

``` ```
01

DI Inputs

Start, stop, reverse, jog, reset, emergency stop, external fault, multi-speed, and command switching.

02

AI / AO

0–10V or 0/4–20mA speed reference and analog feedback output with correct jumper selection.

03

DO / Relay / RS485

Fault output, running output, frequency detection, PLC/HMI status, and RS485 communication.

2. Applies To

Product SeriesSlanvert Hope65 Series Smart AC Drive / VFD
Small ModelsHope65GS2 0.75 kW to 1.5 kW models with DI1–DI4 control input structure.
Larger ModelsHope65GS2 2.2 kW to 5.5 kW and Hope65GT4 0.75 kW to 22 kW models with DI1–DI5 control input structure.
Control ScopeExternal start/stop, forward/reverse, jog, reset, emergency stop, external fault, analog speed, output status, relay fault output, and RS485 wiring.
User LevelQualified electrical technician, panel builder, machine integrator, maintenance engineer, or automation engineer.

3. Hope65 Control Wiring Architecture

Control wiring can be understood as five groups: command inputs, speed reference inputs, output feedback, relay output, and communication. The VFD must be configured to listen to the same control source that is actually wired.

Control Signal Flow

```
01
Command Input
  • DI1–DI5
  • RUN / FWD / REV
  • Jog / reset
  • Stop / fault input
+
02
Speed Reference
  • AI1 0–10V
  • AI1 0/4–20mA
  • Potentiometer
  • Pulse / Modbus
03
Hope65 Logic
  • F0 command source
  • F0 frequency source
  • F6 input functions
  • F7 output functions
04
Output Feedback
  • AO1 analog output
  • DO digital output
  • RA/RB/RC relay
  • Running / fault status
+
05
Communication
  • RS485A
  • RS485B
  • Modbus RTU
  • PLC / HMI / SCADA
Commissioning Rule:

First run the motor from the keypad. After keypad operation is verified, change to terminal, analog, or RS485 control and test one function at a time.

```

4. Control Terminals: Hope65GS2 0.75 kW to 1.5 kW

Smaller Hope65GS2 models use a compact control terminal layout. Confirm the actual terminal markings on the product before wiring.

CategoryTerminalFunctionTypical Use
CommunicationRS485A / RS485BRS485 differential positive/negative communication terminals.PLC, HMI, SCADA, Modbus RTU communication.
Analog inputAI1Analog voltage/current input. Can also be used as DI through parameter setting.0–10V or 0/4–20mA speed reference.
Analog outputAO1Analog voltage/current output.Frequency/current/status feedback to PLC or meter.
Digital inputDI1 / DI2 / DI3Normal digital inputs.Forward, reverse, jog, reset, stop, fault, multi-speed.
Digital input / pulseDI4Normal digital input or high-frequency pulse input.Multi-speed, pulse input, counter, external signal.
Digital outputDODigital output or high-frequency pulse output.Running output, fault output, frequency detection output.
Power supply10V / GND+10V supply and analog signal ground.Potentiometer reference supply and analog common.
Power supply24V / GND+24V supply and 24V ground.Digital input switching, sensors, contact input wiring.
Relay outputRA / RB / RCRA/RB normally closed, RA/RC normally open.Fault relay, running relay, interlock feedback.

5. Control Terminals: Hope65GS2 2.2 kW to 5.5 kW and Hope65GT4 0.75 kW to 22 kW

Larger Hope65GS2 and Hope65GT4 models include five digital inputs, where DI5 can be used as a normal digital input or high-frequency pulse input.

CategoryTerminalFunctionTypical Use
CommunicationRS485A / RS485BRS485 differential signal positive/negative terminals.Modbus RTU communication with PLC/HMI/SCADA.
Analog inputAI1Analog voltage/current input. Can also be used as DI with parameter setting.0–10V, 4–20mA, or external speed command.
Analog outputAO1Analog voltage/current output.Output frequency, output current, or process feedback signal.
Digital inputDI1 / DI2 / DI3 / DI4Normal digital inputs.Run, reverse, reset, jog, external fault, multi-speed, emergency stop.
Digital input / pulseDI5Normal digital input or high-frequency pulse input.Pulse frequency input, counter, speed command, multi-speed command.
Digital outputDODigital output or high-frequency pulse output.Running status, fault output, frequency reached output, pulse feedback.
Power supply10V / GND+10V supply and analog ground reference.Potentiometer speed reference.
Power supply24V / COM+24V supply and 24V common.Digital input switching and source/sink wiring.
Relay outputRA / RB / RCRA/RB normally closed, RA/RC normally open.Fault relay, running status, alarm or interlock output.

6. Jumper Settings: AI, AO, Source/Sink, DO Ground, and Noise Reference

Jumpers physically change how the terminal behaves. Always confirm the jumper position on the actual control board before connecting external devices.

JumperFunctionTypical Factory SettingWhen to Change
J13 AI1Selects AI1 voltage input or current input.0–10V voltage input.Change when AI1 must accept 0/4–20mA current signal.
J10 AO1Selects AO1 voltage output or current output.0–10V voltage output.Change when PLC/meter expects 0/4–20mA feedback.
J12 PWSelects source-type or sink-type digital input wiring method.Source type.Change when NPN/PNP or external controller wiring requires different DI logic.
J11 CMEControls digital output ground isolation/common behavior.Internally shorted to COM/GND depending model.Disconnect when DO is driven by external power supply as required by wiring method.
J16 / J17Selects whether COM/GND is connected to PE.Disconnected.Use only when interference troubleshooting requires COM/GND to PE reference.
Jumper warning: Wrong jumper selection is a common cause of analog speed not working, unstable feedback, terminal start not working, and PLC signal mismatch. Do not change jumpers without confirming the actual field device signal type.

7. Digital Input Wiring: DI1 to DI5

Digital inputs are used to send ON/OFF commands to the drive. A DI terminal can be assigned to forward run, reverse run, reset, jog, free stop, external fault, multi-speed command, emergency stop, PID pause, control command switching, and other functions.

Digital Input Wiring Logic

```
Internal 24V Control

Uses Hope65 24V and COM/GND terminals with contact or field device input.

External Controller

Uses PLC or sensor output. J12 jumper and common reference must match wiring method.

Active Logic

DI can be active-high or active-low depending on F6 active-mode setting.

DI wiring rule: Use shielded cable where possible, keep wiring short, avoid routing with motor cables, and confirm source/sink/NPN/PNP logic before commissioning.
```
DI FunctionTypical UseImportant Check
Forward run / run commandExternal start command from selector switch or PLC output.Command source must be set to terminal control.
Reverse run / directionReverse rotation or direction selection.Use only when reverse operation is mechanically safe.
Fault resetReset VFD fault through external button or PLC.Do not reset repeatedly without correcting fault cause.
Forward jog / reverse jogShort manual movement for commissioning or positioning.Jog frequency and jog ramp parameters must be safe for machine.
External fault inputStops drive when external device reports fault.Active-high/active-low logic must match safety chain wiring.
Emergency stop / free stopFast command interruption or external stop logic.This does not replace a proper machine safety circuit or mechanical brake where required.
Multi-speed commandSelect preset speeds through DI combinations.Confirm speed table values before production run.

8. Terminal Command Modes: Two-Wire and Three-Wire Control

Terminal command mode defines how external contacts or PLC outputs control RUN, STOP, and direction. Choose the mode that matches the actual wiring.

ModeHow It WorksTypical WiringCommon Mistake
Two-wire mode 1Forward and reverse are controlled by two maintained DI states.DI1 = forward, DI2 = reverse.Both ON or both OFF can stop the drive depending logic.
Two-wire mode 2One DI acts as run enable, another DI selects direction.DI1 = run enable, DI2 = direction selection.Run enable is missing, so motor never starts.
Three-wire mode 1Stop/enable input must remain active; forward and reverse are momentary commands.DI3 = three-wire enable, DI1/DI2 = forward/reverse buttons.Enable circuit open, so start button has no effect.
Three-wire mode 2Enable, run command, and direction state are separated.DI3 = enable, DI1 = run command, DI2 = direction.Panel pushbutton design does not match selected parameter mode.
Practical commissioning rule: If terminal start does not work, return to keypad mode and confirm keypad RUN works first. Then set terminal command mode and test DI input status one by one.

9. Analog Input Wiring: AI1, 10V, and GND

AI1 is commonly used for speed reference from a potentiometer, PLC analog output, process controller, or sensor. It can accept voltage or current input depending on jumper and parameter settings.

Analog Speed Reference Options

```
Potentiometer

Use 10V, AI1, and GND. The wiper signal goes to AI1.

PLC 0–10V

PLC analog output signal goes to AI1, common reference goes to GND.

4–20mA

Set AI jumper for current input and configure frequency source/scaling correctly.

```
CheckCorrect ConditionProblem If Wrong
AI jumperJ13 matches the actual signal: voltage or current.Speed command may stay at 0 Hz or scale incorrectly.
Frequency sourceF0 frequency source is set to analog input when AI controls speed.Drive ignores analog signal.
Cable shieldingShielded cable used, routed away from motor and power cables.Unstable speed, random frequency changes, noise-related behavior.
Signal lengthAnalog wiring kept as short as possible and ideally not more than 20 m.Weak analog signal becomes noisy or inaccurate.
Common referencePLC/sensor analog common is correctly connected to GND reference.AI voltage may float or read incorrectly.

10. Analog Output Wiring: AO1

AO1 can be used to send an analog feedback signal to PLC, meter, indicator, or monitoring device. The output type must match the receiving device.

AO RequirementSetup CheckPractical Note
0–10V outputJ10 set for voltage output.Use when PLC/meter analog input expects voltage.
0/4–20mA outputJ10 set for current output.Use when receiver expects current loop feedback.
Stable feedbackShielded signal cable, correct GND reference, separate routing.Avoid running AO cable with U/V/W motor cable.

11. Digital Output and Relay Output Wiring

The Hope65 provides a digital output terminal and a relay output. These are used for running status, fault output, frequency reached output, or other configured output indications.

Output Signal Options

```
DO Terminal

Can work as digital output or high-speed pulse output depending parameter configuration.

Relay RA/RB/RC

Use for fault output, running status, alarm, or interlock feedback to the panel.

Relay Coil Protection

Install absorption/flyback diode when DO drives a relay coil.

```
OutputUseImportant Warning
DODigital output, open collector function, or high-speed pulse output depending setup.Do not exceed output drive capacity. Use relay coil suppression diode where needed.
RA/RBNormally closed relay contact.Confirm whether the panel logic expects normally closed behavior.
RA/RCNormally open relay contact.Confirm relay output function parameter before using as fault or run signal.

12. RS485 Communication Wiring: RS485A and RS485B

RS485 is used for Modbus communication with PLC, HMI, SCADA, data logger, or remote controller. This article covers wiring-level checks only. Register addresses and Modbus command details should be handled in the dedicated RS485 Modbus setup article.

CheckCorrect ConditionProblem If Wrong
A/B polarityRS485A and RS485B connected according to master device convention.No communication or timeout fault.
Cable typeTwisted-pair shielded communication cable preferred.Noise, unstable communication, CRC errors, random timeout.
Cable routingRS485 cable separated from motor cable and power cable.Communication works at stop but fails during motor running.
Communication parametersDrive address, baud rate, parity, and timeout match the master.Master cannot read/write drive data.

13. Parameters Commonly Required for Control Terminal Setup

Wiring alone is not enough. The drive parameters must match the control method.

Parameter / GroupPurposeWhen to Check
F0-21Command source selection: keypad, terminal, or communication.When RUN key or terminal start does not work as expected.
F0-02Frequency source selection: digital, analog, pulse, PID, communication, etc.When motor starts but output frequency remains 0 Hz or speed reference is ignored.
F6-00 to F6-04Assigns functions to DI terminals.When wiring external pushbuttons, selector switches, PLC outputs, reset, jog, or multi-speed.
F6 DI active modeDefines active-high or active-low state of digital inputs.When an input appears inverted or active when it should be inactive.
F6 terminal command modeSelects two-wire or three-wire terminal command logic.When external start/stop wiring does not match drive behavior.
F6 AI curve / filterScales and filters analog input signal.When analog speed is unstable, nonlinear, reversed, or not reaching max/min speed.
F7 groupConfigures AO, DO, and relay output functions.When fault relay, running output, or feedback output does not match expected signal.
P0 groupCommunication parameters for RS485/Modbus.When PLC/HMI communication command or monitoring does not work.

14. Control Wiring Commissioning Checklist

Use this checklist before moving from keypad operation to external control.

No.CheckPass Condition
1Keypad testMotor runs correctly from keypad at low frequency.
2Command sourceF0-21 set to terminal or communication only after local test succeeds.
3Frequency sourceF0-02 matches digital, analog, pulse, or communication speed command.
4DI assignmentF6 DI functions match actual wiring and machine logic.
5Source/sink wiringJ12 and wiring match NPN/PNP or internal/external 24V method.
6AI signalAI voltage/current measured correctly and J13 matches signal type.
7Output signalsDO, AO, and relay output functions are configured and tested.
8Cable routingControl, analog, and communication wiring routed separately from motor/power wiring.

15. Common Control Wiring Problems and Fixes

ProblemLikely CauseCorrective Action
Motor runs from keypad but not from terminalF0-21 still set to keypad, DI wiring wrong, source/sink mismatch, wrong terminal mode.Set command source to terminal, verify DI status, check J12, and confirm two-wire/three-wire mode.
Motor starts but speed stays 0 HzFrequency source is wrong or analog signal is missing.Check F0-02, AI signal, J13, and frequency reference value.
Analog speed fluctuatesAnalog cable noise, long cable, poor shielding, wrong ground reference.Use shielded cable, separate route, confirm GND, add filtering/ferrite if needed.
PLC output does not activate DINPN/PNP mismatch, J12 wrong, no common reference, wrong active mode.Match PLC output type with source/sink wiring and F6 active-mode setting.
Fault relay logic invertedPanel uses NO contact but wired to NC, or relay output parameter mismatch.Check RA/RB/RC wiring and output function parameter.
RS485 works at stop but fails during motor runCommunication cable routed near U/V/W motor cable or poor shielding.Separate cable route, use shielded twisted pair, verify grounding and termination practice.

16. Do Not Do These During Control Wiring

  • Do not wire control terminals while power is ON.
  • Do not run analog or RS485 cables together with motor U/V/W cables.
  • Do not assume DI logic until source/sink and active-high/active-low settings are confirmed.
  • Do not connect external voltage into terminals without checking the terminal rating and common reference.
  • Do not use DO output to drive a relay coil without proper diode suppression.
  • Do not use VFD terminal stop as the only safety device for emergency stop applications.
  • Do not change AI/AO jumpers without confirming whether the signal is voltage or current.
  • Do not troubleshoot terminal control before proving keypad operation.
  • Do not repeatedly reset faults from a DI reset command before identifying the fault cause.
  • Do not connect COM/GND to PE unless required for interference troubleshooting and approved by the panel design.

17. Stop and Contact Technical Support If

  • The motor runs from keypad but terminal command does not work after DI logic is checked.
  • The analog input signal is correct at the PLC but not recognized by the VFD.
  • RS485 communication repeatedly fails even with correct address, baud rate, parity, and A/B wiring.
  • There is electrical noise, random start/stop behavior, or unstable frequency reference.
  • The panel uses mixed internal and external 24V supplies and common wiring is unclear.
  • The application includes emergency stop, safety interlock, hoist, lift, crane, or hazardous machine control.
  • You are unsure whether the PLC output is NPN, PNP, relay, sinking, or sourcing type.
  • There is visible damage, burning smell, abnormal heating, or control-board damage suspected.

18. Information to Share With Technical Support

To reduce troubleshooting time, share the following information:

  • Photo of Hope65 drive nameplate
  • Photo of control terminal wiring
  • Model and power rating of the Hope65 drive
  • Whether the motor runs from keypad at 5 Hz to 10 Hz
  • Required control method: keypad, terminal, analog, PLC, HMI, or RS485
  • F0-21 command source setting
  • F0-02 frequency source setting
  • DI terminal function settings from F6 group
  • Terminal command mode: two-wire or three-wire
  • J13 AI jumper position and AI signal type
  • J12 source/sink jumper position
  • Measured voltage/current at AI1 if analog speed is used
  • PLC output type: relay, NPN, PNP, sinking, or sourcing
  • RS485 address, baud rate, parity, and A/B wiring photo if communication is used
  • Fault code shown on keypad, if any

Need Help With Hope65 Control Wiring?

```

Smidnya technical support can help review your control wiring, DI logic, AI signal, relay output, RS485 connection, PLC output type, command source, frequency source, and terminal parameter setup before commissioning.

Share control terminal photo + F0-21/F0-02 + DI settings for faster support
```
  • Hope65 Series Smart AC Drive / VFD Quick Start Guide: Wiring, Setup, and First Motor Run
  • Hope65 Series Smart AC Drive / VFD Motor Not Running: Step-by-Step Troubleshooting
  • Hope65 Series Smart AC Drive / VFD Standard Power Wiring Guide
  • Hope65 Series Smart AC Drive / VFD RS485 Modbus Communication Setup
  • Hope65 Series Smart AC Drive / VFD Potentiometer and Analog Speed Control Guide
  • Hope65 Series Smart AC Drive / VFD Fault Codes: Meaning, Causes, and Corrective Actions