IS 108 MM/2NO-2E0 Inductive switch

IS 108 MM/2NO-2E0 Inductive switch

Technical Data Sheet

Inductive Switch

Part No.: 50129926
Model: IS 108 MM/2NO-2E0
Manufacturer: Leuze electronic GmbH + Co. KG
📅 Date: 2025-04-04


Contents

  1. Technical Data

  2. Dimensioned Drawings

  3. Electrical Connection

  4. Diagrams

  5. Operation and Display

  6. Part Number Code

  7. Notes

  8. Certifications & Classification

  9. Contact Information


1. Technical Data

Basic Data

  • Series: 108

  • Typical Operating Range Limit (Sn): 2 mm

  • Operating Range (Sa): 0 ... 1.6 mm


Electrical Data

  • Protective Circuits:

    • Overload protection

    • Polarity reversal protection

    • Short circuit protected

  • Supply Voltage (UB): 10 ... 30 V DC

  • Residual Ripple: 10 % of UB

  • Open-Circuit Current: 0 ... 10 mA

  • Temperature Drift (max): 10 % of Sr

  • Repeatability (max): 1 % of Sr

  • Switching Hysteresis: 15 %


Outputs

  • Number of Digital Switching Outputs: 1 piece(s)

  • Voltage Type: DC

  • Switching Current (max): 100 mA

  • Residual Current (max): 0.01 mA

  • Voltage Drop: ≤ 2 V

  • Switching Output Type:

    • Switching Element: Transistor, NPN

    • Switching Principle: Normally Open (NO)


Time Behavior

  • Switching Frequency: 3,000 Hz


Connection

  • Number of Connections: 1 piece(s)

Connection 1:

  • Function: Signal OUT

  • Voltage Supply Type: Cable

  • Cable Length: 2,000 mm

  • Sheathing Material: PVC

  • Cable Color: Black

  • Number of Conductors: 3-wire

  • Wire Cross Section: 0.18 mm²


2. Dimensioned Drawings

  • Design: Cylindrical

  • Dimensions (Ø x L): 8 mm x 45 mm

  • Thread Size: M8 x 1 mm

  • Installation Type: Embedded

  • Housing Material: Nickel-plated brass

  • Sensing Face Material: Plastic (POM - Polyoxymethylene)

  • Housing Color: Red (RAL 3000) and Silver

  • Fastening Type: Mounting Thread

  • Standard Measuring Plate: 8 x 8 mm², Fe360

Mounting Distances

ParameterValue
Sn2 mm
D10 mm
D28 mm
D38 mm
3Sn

3. Electrical Connection

Connection 1 (Cable - 3-wire, 2000 mm):

  • Color Codes and Assignments:

Wire ColorFunction
BrownV+
BlueGND
BlackOUT 1

4. Diagrams

  • Not provided in image form

  • Refer to official technical diagram or product documentation via www.leuze.com


5. Operation and Display

  • Type of Display: LED

  • Number of LEDs: 1

  • LED Color: Yellow

  • LED Status Meaning:

    • Continuous Light: Switching output/switching state active


6. Part Number Code

Format: ISX YYY XX / ZZZ – AAA – DDD

CodeDescription
ISXInductive Switch Type (IS = Standard, ISS = Short design)
YYYSeries (108 = M8 x 1 external thread)
XXHousing (MM = Metal housing, plastic active face)
ZZZOutput type (2NO = NPN Transistor, NO contact)
AAARange/Installation (2E0 = 2.0 mm, Embedded)
DDDElectrical Connection (n/a = Cable 2000 mm, 3-wire)

7. Notes

  • ⚠️ Important Usage Restrictions:

    • This is not a safety sensor

    • Do not use for personnel protection

    • Only to be commissioned by qualified personnel

    • Follow the product’s intended use strictly


8. Certifications and Classification

  • Degree of Protection: IP67

  • Standards Applied: IEC 60947-5-2

Customs & Classification Codes

  • Customs Tariff Number: 85365019

  • ECLASS Codes:

    • ECLASS 5.1.4 to 11.0: 27270101

    • ECLASS 12.0 to 15.0: 27274001

  • ETIM Codes:

    • ETIM 5.0 to 10.0: EC002714

9.  Troubleshooting Guide 

IssuePossible CauseRecommended Action
No LED indicationNo power supplyVerify 10–30 V DC is supplied correctly to the sensor (brown to V+, blue to GND)
Loose wiring or broken cableCheck cable continuity and ensure all wires are properly connected
Internal faultReplace sensor if wiring and power are correct
LED ON but output not switchingTarget object not within sensing range (Sn = 2 mm)Ensure the target is within 1.6 mm operating range
Target material not suitableUse standard Fe360 metal as target (correction factor = 1)
False switching (intermittent signal)Excessive vibration or unstable mountingSecure the sensor properly using the M8 x 1 thread
Electrical noise/interferenceCheck for proper grounding; isolate sensor wires from high-power lines
Sensor switches continuouslyMetallic dust or object permanently in frontClean sensing face and remove interfering objects
Short circuit in output lineCheck load wiring, replace sensor if damaged
Short sensor lifespanOverload on switching output (>100 mA)Ensure the output current does not exceed 100 mA
Incorrect power polarityUse proper polarity (brown = V+, blue = GND)
Cable damageExcessive bending or mechanical strainUse protective routing and strain relief for cable