Part No.: 50129926
Model: IS 108 MM/2NO-2E0
Manufacturer: Leuze electronic GmbH + Co. KG
📅 Date: 2025-04-04
Technical Data
Dimensioned Drawings
Electrical Connection
Diagrams
Operation and Display
Part Number Code
Notes
Certifications & Classification
Contact Information
Series: 108
Typical Operating Range Limit (Sn): 2 mm
Operating Range (Sa): 0 ... 1.6 mm
Protective Circuits:
Overload protection
Polarity reversal protection
Short circuit protected
Supply Voltage (UB): 10 ... 30 V DC
Residual Ripple: 10 % of UB
Open-Circuit Current: 0 ... 10 mA
Temperature Drift (max): 10 % of Sr
Repeatability (max): 1 % of Sr
Switching Hysteresis: 15 %
Number of Digital Switching Outputs: 1 piece(s)
Voltage Type: DC
Switching Current (max): 100 mA
Residual Current (max): 0.01 mA
Voltage Drop: ≤ 2 V
Switching Output Type:
Switching Element: Transistor, NPN
Switching Principle: Normally Open (NO)
Switching Frequency: 3,000 Hz
Number of Connections: 1 piece(s)
Connection 1:
Function: Signal OUT
Voltage Supply Type: Cable
Cable Length: 2,000 mm
Sheathing Material: PVC
Cable Color: Black
Number of Conductors: 3-wire
Wire Cross Section: 0.18 mm²
Design: Cylindrical
Dimensions (Ø x L): 8 mm x 45 mm
Thread Size: M8 x 1 mm
Installation Type: Embedded
Housing Material: Nickel-plated brass
Sensing Face Material: Plastic (POM - Polyoxymethylene)
Housing Color: Red (RAL 3000) and Silver
Fastening Type: Mounting Thread
Standard Measuring Plate: 8 x 8 mm², Fe360
Parameter | Value |
---|---|
Sn | 2 mm |
D1 | 0 mm |
D2 | 8 mm |
D3 | 8 mm |
≥ | 3Sn |
Connection 1 (Cable - 3-wire, 2000 mm):
Color Codes and Assignments:
Wire Color | Function |
---|---|
Brown | V+ |
Blue | GND |
Black | OUT 1 |
Not provided in image form
Refer to official technical diagram or product documentation via www.leuze.com
Type of Display: LED
Number of LEDs: 1
LED Color: Yellow
LED Status Meaning:
Continuous Light: Switching output/switching state active
Format: ISX YYY XX / ZZZ – AAA – DDD
Code | Description |
---|---|
ISX | Inductive Switch Type (IS = Standard, ISS = Short design) |
YYY | Series (108 = M8 x 1 external thread) |
XX | Housing (MM = Metal housing, plastic active face) |
ZZZ | Output type (2NO = NPN Transistor, NO contact) |
AAA | Range/Installation (2E0 = 2.0 mm, Embedded) |
DDD | Electrical Connection (n/a = Cable 2000 mm, 3-wire) |
⚠️ Important Usage Restrictions:
This is not a safety sensor
Do not use for personnel protection
Only to be commissioned by qualified personnel
Follow the product’s intended use strictly
Degree of Protection: IP67
Standards Applied: IEC 60947-5-2
Customs Tariff Number: 85365019
ECLASS Codes:
ECLASS 5.1.4 to 11.0: 27270101
ECLASS 12.0 to 15.0: 27274001
ETIM Codes:
ETIM 5.0 to 10.0: EC002714
Issue | Possible Cause | Recommended Action |
---|---|---|
No LED indication | No power supply | Verify 10–30 V DC is supplied correctly to the sensor (brown to V+, blue to GND) |
Loose wiring or broken cable | Check cable continuity and ensure all wires are properly connected | |
Internal fault | Replace sensor if wiring and power are correct | |
LED ON but output not switching | Target object not within sensing range (Sn = 2 mm) | Ensure the target is within 1.6 mm operating range |
Target material not suitable | Use standard Fe360 metal as target (correction factor = 1) | |
False switching (intermittent signal) | Excessive vibration or unstable mounting | Secure the sensor properly using the M8 x 1 thread |
Electrical noise/interference | Check for proper grounding; isolate sensor wires from high-power lines | |
Sensor switches continuously | Metallic dust or object permanently in front | Clean sensing face and remove interfering objects |
Short circuit in output line | Check load wiring, replace sensor if damaged | |
Short sensor lifespan | Overload on switching output (>100 mA) | Ensure the output current does not exceed 100 mA |
Incorrect power polarity | Use proper polarity (brown = V+, blue = GND) | |
Cable damage | Excessive bending or mechanical strain | Use protective routing and strain relief for cable |